Datacenters


Datacenter Luxembourg is providing datacenter services out of distinct geographical facilities connected to a looped backbone.

The hosting facilities answer the customers' specific needs while respecting a series of criteria concerning accessibility, security and availability.

Do not hesitate to contact us to plan a visit!


DCL01:
Windhof

DCL02: Cloche d'Or

DCL-NOC:
2, rue Léon Laval
L-3372 Luxembourg

Phone: +352 261916-1
Fax: +352 26202996

Email: This e-mail address is being protected from spambots. You need JavaScript enabled to view it

dc_picture1

DCL01 - Windhof Data Centre

Data Floor
Surface 5.000 m2
Rack area - 70 m2 equipped with lockable racks (2000x800x600), private & shared
- Available rack sizes 1-4 RU, 1/2 rack, Full Rack
Cage area steel cages in various sizes
Floor load - 1.500 Kg/m2, more on demand
Raised floors 1.000 mm
Headspace 4.4 m
Cabling - Above head cable conduits
- Raised floor cable conduits
Main Power
Electrical Power 935 VA/m2 (upgrade possible)
Redundancy - Dual power supply chain 2*(N+1)
- Redundant transformers 2*(11+1)
Grounding Faraday cage inherent to the building design to ensure the integrity into the IT rooms
Automatic fail over (UPS) - 2*(N+1) with integrated Diesel Power generators
autonomy 5 days
Air Cooling
Power 750 W/m2 (upgrade possible)
- Dual air cooling supply chain 25(N+1)
- Redundant alr handling units with filtering systems
Relative humidity 50% (± 8%), temperature 24°C (± 2°C) at air return level
Air renewal: 1 m3/h/m2
Customisable air cooling implementation
Fire Security
Detection systems Fluid, Gas, Smoke (dual system)
Fire extinction system N+1 with neutral gas
Fire alarm: Direct alarm connection to Luxembourg City`s Fire Brigade
Fire resistance: - Doors / Walls REI 30/F90
Public accreditation - ITM certification
- Fire Brigade certification
Water - Water leakage detection system
- Water flow regulation for technical systems and rainwater
Access
Visitors - "Accredited visitors only" policy
- Guest area with attached meeting room
- Escorted visits
Access to the building and IT-Rooms - nominative badges with redundant management system
Physical intrusion prevention and detection: - Temper resistant windows/doors
- Break-into and motion detectors
- Manned patrols
- CCTV in/outside surveillance system
- Access to CCTV and environment data over secured Internet
- 7-day round robin video recording
Communications
Fibre connections FiberIP, P&T, Telenet, Cegecom, BT, COLT, BCE, MCI
Copper connection FiberIP, P&T
Internet access Direct backbone connection
Sattelite feed - ASTRA 1&2
- HOTBIRD
- POUR 8
Internal cabling: Cat. 7, Secured WLAN 802,11 (a/b)
Roof top available - GPS based SMPTE time generator
- Dedicated news feeds
- General free-to-air broadcasts reception dishes
- Dedicated microwave links
Convenience
Equipment delivery and handling - Goods elevators (max 3 500 kgs) / People lift
- Separate supplier access with secured staging and testing area
Additioanl Services - Reception services on request
- Catering services on request

DCL02 - Cloche d`Or Data Centre

Data Floor
Surface 700 m2
Rack area - 45 m2 equipped with lockable racks (2000x800x600)
- Available rack sizes 1/2 rack, Full Rack
Cage area 655m2, steel cages in various sizes
Floor load - Standard 500 Kg/m2, more on demand
- Additional load capacity up to 1.200 Kg/m2, more on demand
Raised floors 600 mm
Headspace 3 m
Cabling - Above head cable conduits
- Raised floor cable conduits
Main Power
Total Power 850 KVA secured
IT equipment 600 KVA secured
Utility/Cooling 250 KVA secured
Grounding - Mashed net
- Resistance 10 M Ohm
Automatic fail over Yes, UPS and power generator
Backup Power Generator
Power 850 KVA
Diesel 10.000 Liters
Autonomy Min. 48 hours @ 100% charge
UPS
Power 750 W/m2
Compressor 2x330 KW
Cooling tower 670 KW @ 35°C outside temperature
Cooling media NH3 (Ammonia)
Downflow air conditioning 8 units
Fresh air production 20.000m3/hour
Fire Security
Detection systems Fluid, Gas, Smoke (dual system)
Fire extinction system N+1 with Argonite (50% Nitrogen & 50% Argon) inert gas system
Fire alarm: Direct alarm connection to Luxembourg City`s Fire Brigade
Fire resistance: - Exterior Walls F90
- Doors T60
Public accreditation - ITM certification
- Fire Brigade certification
Access
Visitors - "Accredited visitors only" policy
- Guest area with attached meeting room
Access to the premises Anonymous badges plus security codes
Access to the data centre - One-man only air-lock system
- Badges and security codes
Physical intrusion prevention and detection: - Temper resistant windows/doors
- Break-into and motion detectors
- Manned patrols
- CCTV in/outside surveillance system
- Access to CCTV and environment data over secured Internet
- 7-day round robin video recording
Equipment delivery and handling - Secured loading dock
- Take-in, Take-out policy
- Separate HW maintenance lab
Communications
Fibre connections

FiberIP, P&T, Telenet, Cegecom, BT, COLT, BCE, MCI

Copper connection FiberIP, P&T
Internet access Direct backbone connection
Sattelite feed - ASTRA 1&2
- HOTBIRD
- POUR 8
Internal cabling: Cat. 7, Secured WLAN 802,11 (a/b)
Roof top available - GPS based SMPTE time generator
- Dedicated news feeds
- General free-to-air broadcasts reception dishes
- Dedicated microwave links